Multi-loop digital display control instrument with automatic SMD packaging technology, has a strong anti-jamming capability. It can be used in conjunction with various sensors、transmitters to display temperature, pressure, liquid level, speed, force and other physical parameters, and it can measure 8~16 loops input go the rounds, support 8~16 loops “uniform alarm output”, “16 loops separate alarm output”, “uniform transition output ”, “8 loops separate transition output” and 485/232 communication, and is applicable in system with various measuring points. Features Double four-digit LED display;3 types of dimensions available;Standard snap-in installation;Power supply: AC/DC100~240V (Frequency 50/60Hz)Power consumption≤5W DC 20~29V Power consumption≤3W


Product Detail

Product Tags

  • Specification
 Product Multi-loop digital display controller
 Model SUP-2700
 Dimension A. 160*80*136mm
B. 80*160*136mm
C. 96*96*136mm
Measurement accuracy ±0.2%FS
Transmission output Analog output—-4-20mA、1-5v、
0-10mA、0-5V、0-20mA、0-10V
Alarm Output Over-range display value flashing alarm function

With upper and lower limit alarm function, with alarm return difference setting;Relay capacity:
AC220V/2A(big)DC24V/2A(big)(Resistive load)
Note: When the load exceeds the relay contact capacity, please do not directly carry the load

Power supply AC/DC100~240V (Frequency 50/60Hz)  Power consumption≤5W
DC 20~29V  Power consumption≤3W
Use environment Operating temperature(-10~50℃)No condensation, no icing
Printout RS232 printing interface, micro-matched printer can realize manual, timing and alarm printing functions

 

  • Introduction

Multi-loop digital display control instrument with automatic SMD packaging technology, has a strong anti-jamming capability. It can be used in conjunction with various sensors、transmitters to display temperature, pressure, liquid level, speed, force and other physical parameters, and it can measure 8~16 loops input go the rounds, support 8~16 loops “uniform alarm output”, “16 loops separate alarm output”, “uniform transition output ”, “8 loops separate transition output” and 485/232 communication, and is applicable in system with various measuring points.

Input signal type list:

Graduation Number Pn Signal type Measure range Graduation Number Pn Signal type Measure range
0 TC B 400~1800℃ 18 Remote Resistance 0~350Ω -1999~9999
1 TC S 0~1600℃ 19 Remote Resistance 3 0~350Ω -1999~9999
2 TC K 0~1300℃ 20 0~20mV -1999~9999
3 TC E 0~1000℃ 21 0~40mV -1999~9999
4 TC T -200.0~400.0℃ 22 0~100mV -1999~9999
5 TC J 0~1200℃ 23 -20~20mV -1999~9999
6 TC R 0~1600℃ 24 -100~100mV -1999~9999
7 TC N 0~1300℃ 25 0~20mA -1999~9999
8 F2 700~2000℃ 26 0~10mA -1999~9999
9 TC Wre3-25 0~2300℃ 27 4~20mA -1999~9999
10 TC Wre5-26 0~2300℃ 28 0~5V -1999~9999
11 RTD  Cu50 -50.0~150.0℃ 29 1~5V -1999~9999
12 RTD  Cu53 -50.0~150.0℃ 30 -5~5V -1999~9999
13 RTD  Cu100 -50.0~150.0℃ 31 0~10V -1999~9999
14 RTD  Pt100 -200.0~650.0℃ 32 0~10mA square -1999~9999
15 RTD  BA1 -200.0~600.0℃ 33 4~20mA square -1999~9999
16 RTD  BA2 -200.0~600.0℃ 34 0~5V square -1999~9999
17 Linear resistance 0~400Ω -1999~9999 35 1~5V square -1999~9999